BHP BILLITON HILLSIDE ALUMINIUM SMELTER RATING: 1075 Kvar VOLTAGE: 22 kV
ANALYSIS/DIAGNOSIS THERMAL FAULT OF OF HIGH TEMPERATURE RANGE>700 Deg C (IEC 599: GAS PRODUCTION RATES-Ethylene(C2H4)-Significant CONDITION 4 FINDINGS: Burning on the Resistor CAUSES: Fourth Harmonic being amplified causing the transformer to be subjected to 10 times its rated current(milli seconds) i.e Design Fault System
SAVINGS IN THE MILLION RANGE or in the Billion Range due the knock on effect
|